Leave Your Message

       
VS-W250-500 Partial Discharge Free AC Withstand Voltage Test System - WESHINE ELECTRIC MANUFACTURING CO.,LTD

VS-W250-500 Partial Discharge Free AC Withstand Voltage Test System

The VS-W50-250 Partial Discharge Free AC Withstand Voltage Test System is a high-performance testing solution designed for AC withstand voltage testing and partial discharge measurement of transformers, switchgear, GIS, insulators, cables, bushings, and other high-voltage electrical equipment. Utilizing advanced SF6 gas-insulated transformer technology, the system provides stable 250kV output with an overall partial discharge level of ≤5pC. Featuring intelligent automatic control, reactive power compensation, low-noise operation, and comprehensive protection functions, it is ideal for power utilities, industrial enterprises, universities, research institutes, and high-voltage laboratories.

Product Detail

Product Details

The VS-W250-500 Partial Discharge Free AC Withstand Voltage Test System is engineered to meet the stringent requirements of modern high-voltage insulation testing and partial discharge measurement. Utilizing advanced SF6 gas-insulated transformer technology, the system eliminates the environmental risks associated with traditional oil-immersed test transformers while providing superior insulation performance and long-term operational reliability.

Designed for testing transformers, GIS switchgear, power cables, bushings, insulators, reactors, and other high-voltage apparatus, the system combines a high-voltage test transformer, coupling capacitor, voltage divider, current limiting reactor, low-voltage compensation reactor, isolation transformer, and intelligent control console into a complete testing platform.

The complete testing system maintains a partial discharge level of ≤5pC under rated voltage conditions, making it suitable for factory acceptance testing, type testing, routine insulation verification, and research applications requiring ultra-low partial discharge performance. The output waveform distortion remains below 2%, ensuring accurate and repeatable test results that comply with international testing standards.

The integrated low-voltage compensation reactor significantly reduces power demand while improving system efficiency. Multiple compensation stages allow precise adjustment of reactive power, enabling stable voltage output even under demanding testing conditions.

The control console provides reliable voltage regulation and monitoring functions, allowing operators to perform withstand voltage testing safely and efficiently. Combined with high-voltage overvoltage protection, current-limiting protection, and discharge protection measures, the system ensures maximum safety during high-voltage testing procedures.

With its 500kV output capability, high testing capacity, and excellent partial discharge performance, the VS-W250-500 is an ideal solution for utilities, manufacturers, and laboratories involved in high-voltage equipment testing and insulation evaluation.

 

System Specifications
Parameter Specification
Rated Capacity 250kVA
Input Power Supply Single Phase AC 380V, 50Hz
Rated Output Voltage 500kV
Rated Output Current 0.5A
Working Frequency 50Hz
Output Waveform Pure Sine Wave
Waveform Distortion ≤2%
System Noise ≤50dB
Short Circuit Impedance ≤10%
Partial Discharge Level ≤5pC
Continuous Operation 30 Minutes
Overvoltage Capability 110% Rated Voltage for 1 Minute
Protection Functions Overvoltage & Overcurrent Protection

 

High Voltage Test Transformer Automatic Control Console
Parameter Specification Parameter Specification
Rated Capacity 250kVA Rated Capacity 50kVA
Input Voltage 0–1000V Power Supply AC380V
Output Voltage 500kV Output Voltage 0–400V
Output Current 0.5A Rated Current 125A
Instrument Voltage 100V Operating Mode Manual Control
Insulation Medium SF6 Gas Continuous Operation 30 Minutes
Transformer Type Partial Discharge Free

 

Low Voltage Compensation Reactor
Parameter Specification
Rated Capacity 200kvar
Rated Voltage 1kV
Compensation Accuracy ±5kvar
Adjustment Method Motorized Switching
Regulation Method Multi-Tap Compensation
Fixed Reactors 50kvar + 100kvar
Adjustable Reactor 50kvar, 5 Steps
Compensation Step 10kvar per Step

 

Isolation Transformer
Parameter Specification
Rated Capacity 50kVA
Input Voltage 0.4kV
Output Voltage 1kV
Rated Current 50A / 125A
Filtering Attenuation ≥40dB (40kHz–100kHz)
Filtering Attenuation ≥60dB (100kHz–2MHz)
Insulation Strength 3kV / 1 Minute

 

High Voltage Divider
Parameter Specification
Rated Voltage 500kV
Capacitance 50pF
Divider Ratio 5000:01:00
Measurement Accuracy Class 1.0
Dielectric Loss tgσ ≤0.5%

 

Coupling Capacitor
Parameter Specification
Rated Voltage 500kV
Capacitance 150pF

 

High Voltage Current Limiting Reactor
Parameter Specification
Rated Voltage 500kV
Inductance 100mH

 

Product Guide

How the System Works

The system generates a stable 50Hz high-voltage AC output through an SF6 gas-insulated test transformer. During testing, the coupling capacitor detects partial discharge signals while the voltage divider continuously monitors output voltage. The compensation reactor automatically optimizes reactive power requirements, reducing input current and improving overall efficiency.

The current-limiting reactor and protection system safeguard both the test object and the equipment from transient overvoltage and discharge events, ensuring safe and reliable testing performance.

Application Scenarios

Power Utility Companies

Used for insulation verification, commissioning tests, and maintenance of transformers, GIS equipment, switchgear, and substation assets.

Transformer Manufacturers

Suitable for routine testing, factory acceptance testing (FAT), and type testing of power transformers and distribution transformers.

High Voltage Laboratories

Provides ultra-low partial discharge testing capabilities for certification, research, and development applications.

Research Institutes and Universities

Supports insulation research, dielectric studies, and high-voltage engineering education.

Industrial and Mining Enterprises

Used for preventive maintenance and insulation condition assessment of critical electrical infrastructure.

Applications

1、Power Transformer Testing

2、GIS Partial Discharge Testing

3、AC Withstand Voltage Testing

4、High Voltage Switchgear Testing

5、Bushing Testing

6、Power Cable Testing

7、Insulator Testing

8、Factory Acceptance Testing (FAT)

9、Type Testing and Certification

10、High Voltage Research Applications

Weshine Advantages

Weshine Electric specializes in the development and manufacturing of high-voltage testing equipment and partial discharge measurement systems. Our VS-W Series Partial Discharge Free AC Withstand Voltage Test Systems combine advanced SF6 insulation technology, ultra-low partial discharge performance, precise voltage measurement, and reliable protection mechanisms. Designed to meet the requirements of utilities, manufacturers, laboratories, and research institutions, Weshine solutions provide accurate, safe, and efficient testing for modern high-voltage power equipment.

Leave Your Message